Request for Proposal (RFP No. 33/MOT/2025) – Preventive Maintenance on the 500MVA Maputo Mozal 2 Transformer 400kV-132kV-22kV – Maputo Substation – Mozambique

Subject: Request for Proposal (RFP No. 33/MOT/2025) – Preventive Maintenance on the 500MVA Maputo Mozal 2 Transformer 400kV-132kV-22kV – Maputo Substation – Mozambique.

1. Background:

The Mozambique Transmission Company- MOTRACO – is a limited liability company incorporated in Republic of Mozambique in 1998. The companies are a joint venture of Electricidade de Moçambique (EDM), Eskom holding (Eskom) and Eswatini Electricity Company (EEC). MOTRACO was created as a vehicle for co-operation with the primary objective of building, owning, operating, maintaining the Transmission system, and supplying electricity to the Mozal aluminium smelter in Mozambique and wheeling power to EEC and EDM.

Terms of Reference

2. Scope of Work:

The contractor is required to conduct 6 yearly preventive maintenance as per scope and equipment below:

Description Item Cycle
Maputo Mozal No2 Trfr Fdr Bay 400kV-132kV-22 kV Trfr Transformer Maintenance 6 Yearly
Maputo Mozal No2 Trfr Fdr Bay 400kV – 132kV-22kV Trfr Bushing Bank 400kV Bushing Tan Delta Test 6 Yearly
Maputo Mozal No2 Trfr Fdr Bay 400kV – 132kV-22kV Trfr Bushing Bank 132kV Bushing Tan Delta Test 6 Yearly
Maputo Mozal No2 Trfr Fdr Bay 400kV – 132kV – 22kV Trfr Bushing Bank 22kV Bushing Tan Delta Test 6 Yearly
Maputo Mozal No2 Trfr Fdr Bay 400kV-132kV-22kV Trfr Neutral Bushing Bank 22kV Bushing Tan Delta Test 6 Yearly
Maputo Mozal No2 Trfr Fdr Bay 400kV-132kV-22kV Trfr TC 400kV Tap Changer Maintenance 6 Yearly

Conditions:

  • All hands tools and scaffolding/cherry pickers/Crane shall be provided by the contractor.
  • The outages for maintenance will be booked as per client and contractor agreement.
  • The Contractor is responsible for providing oil for the Tap Changer and must submit the oil test result results before.

2.1. Specifications:

Transformer Data
Manufacturer ABB Powertech Transformer
Rated Power HV 500 MVA
Rated Power MV 500 MVA
Rated Power LV 40 MVA
Rated Voltage HV 400-15% KV
Rated Voltage MV 132 kV
Rated Voltage LV 22 kV
Rated Current HV 722 A
Rated Current MV 2187 A
Rated Current LV 1050 A
Number of Phases/Frequency 3/50 Hz
Vector Group YNaOd1
Insulation Level HV
Insulation Level MV
Insulation Level LV
Insulation Level YN
LI 1425 AC 420
LI 550 AC 146
LI 150 AC 50
LI 110 AC 38
Type of Cooling ONAN/ONAF
Tap Changer Type ABB On Load UCGRT 650/1050/C
Bushings HV ABB GOE 1675-1175-2500-0.3-B
MV ABB GOE 650-500-3150-0.3-B
LV ABB GOB 250/1250
YN ABB GOB 250/1250

3. Format of Proposal:

A technical and financial proposal shall be submitted, detailing the following:

  • Proposed process/method statement.
  • Labour cost and time.
  • Transport and equipment.
  • Calibration certificate of testing equipment used.
  • Minimum 2 references of works with similar scope.
  • Eskom Authorization (for NORTHEAST GRID) for work in restricted areas.

4. Clarifications:

All clarifications will be given shall be submitted by email to MOTRACO to the attention of:

5. Closing Date:

The proposals must be submitted by email no later than 03:00 PM o’clock of 15 August 2025.
Regards

Adérito Sousa
General Manager

Attachment:

Baseline Maintenance with Scope of Work


Sorry! This job has expired.
PortuguêsptPortuguêsPortuguês